|
|
Sew 855 PRB
|
|
FEATURES
● Two functions in one unit: open phase and phase sequence detection.● Lamps let you determine at-a-glance if phase is open.● Large size alligator clips for easy clipping onto switch-boards terminals.● Checks a wide range of 3-phase power sources.● Special test leads length are available on request.● Push button switch is designed to minimize damage due to negligence.
SPECIFICATIONS
Voltage
200V-600V AC
Frequency response
50 / 60 Hz
Operating temperature & humidity
0°C ~ 40°C at 80% Max. relative humidity
Storage temperature & humidity
-10°C ~ 50°C at 90% Max. relative humidity
Cord
1.1m each of red(R), white(S) and black(T) cord
Dimensions
134(L) × 85(W) × 45(D)mm
Weight
Approx. 530g
Safety standard
EN 61010-1 CAT Ⅳ 600V EN 61010-2-31
|
Phase Sequence Indicators (Contact Type)
|
|
|
|
|
|
|
Sew ST-860
|
|
FEATURES
● Three functions in one unit: open phase, phase sequence and motor rotation indication. ● Large size alligator clips for easy clipping onto switch- boards terminals. ● Highly reliable. ● Identifies 3 phase sequence and open phase check.● Ideal for installing conveyor lines, pump systems and interconnected drivers.
SPECIFICATIONS
Input voltage
100-500V AC
Frequency range
45-70 Hz
Circuit structure
All electronic (not mechanical)
Power requirement
9V (6F22) × 1
Power consumption
Consumption current approx. 14mA of motor rotation field tester
AC power consumption
Approx. 7mA
Dimensions
153(L) × 72(W) × 35(D)mm
Weight (battery included)
Approx. 200g
Safety standard
EN 61010-1 CAT III 500V EN 61326-1
|
Phase Sequence Indicators (Contact Type)
|
|
|
|
|
|
|
Sew 865 PR
|
|
FEATURES
● The 865 PR is a detector with LEDs to show the de- tection better visible than neon. ● Three functions in one unit, including open phase, phase sequence and 3 phase motor rotation.● Designed for checking a wider range of 3 phase power source from 100V to 500V.● Indicates R.S.T LEDs which frequency range from 40Hz to 400Hz.● Wide range detection of motor frequency range from 2Hz to 400Hz.● Fixed magnets for convenient measurement.
SPECIFICATIONS
Measurement principle
Contact Live Wire
Input voltage
100-500Vac
Frequency range
40Hz-400Hz
Operating temperature & humidity
0°C ~ 40°C Max. 80% R.H.
Storage temperature & humidity
-10°C ~ 50°C Max. 80% R.H.
Cable length
Approx. 1m
Dimensions
128(L) x 72(W) x 44(D)mm
Weight (battery included)
Approx. 220g
Power source
9V (6F22) × 1
Safety standard
EN 61010-1 CAT III 500V EN 61326-1 EN 61557-1 ... |
Phase Sequence Indicators (Contact Type)
|
|
|
|
|
|
|
Sew 862 PR
|
|
FEATURES
● Two functions in one unit: open phase and phase sequence detection.● Neon light indicators.● Large size alligator clips for easy clipping onto switch- boards terminals.● Checks a wide range of 3-phase power sources.● Ideal for installing conveyor lines, pump systems and interconnected drivers.● Water proof.● Special test leads length are available on request.
SPECIFICATIONS
Input voltage
100-500V AC
Frequency range
45 - 70 Hz
Circuit structure
All electronic (not mechanical)
AC power consumption
Approx. 7mA
Dimensions
102(L) × 78(W) × 32.5(D)mm
Weight
862 PR : 115g Test leads : 97g Total : Approx. 212g
Safety standard
EN 61010-1 CAT III 500V / CAT IV 300V EN 61326-1
|
Phase Sequence Indicators (Contact Type)
|
|
|
|
|
|
|
Sew 863 PR
|
|
FEATURES
● Two functions in one unit: open phase and phase sequence detection.● Neon light indicators.● Large size alligator clips for easy clipping onto switch- boards terminals.● Allows you to check a wide range of 3-phase power sources.● Special test leads length are available on request.
SPECIFICATIONS
Input voltage
100-500V AC
Frequency range
45 - 70 Hz
Circuit structure
All electronic (not mechanical)
AC power consumption
Approx. 7mA
Dimensions
102(L) × 78(W) × 32.5(D)mm
Weight
Approx. 228g
Safety standard
EN 61010-1 CAT III 500V EN 61326-1
|
Phase Sequence Indicators (Contact Type)
|
|
|
|
|
|
|
Sew 887 PR
|
|
FEATURES
● Indicates phase rotation. ● Indicates phase presence.● No battery required.● Phase rotation phase presence indicated on large liquid crystal display.● Small, rugged enclosure.● Color coded test leads.● Phase presence indication from as low as 40Vac to as high as 500Vac.● Fused.● Lightweight, robust and compact.● EN 61010-1 CAT III 500V EN 61010-2-032
SPECIFICATIONS
ELECTRICAL
Determination of the Phase Presence
Nominal Voltage for Phase Presence Indication (the voltage required for the LCD L1, L2, L3 indicators to come on)
From 40Vac to 500Vac.
Frequency range
From 15Hz to 400Hz.
Determination of the Phases Rotary Field Direction:
Direction Indication by LCD Display(the voltage required to have the LCD Direction Arrows to indicates and the L1 L2 L3 or L3 L2 L1 indicators to show)
From 40 to 500Vac.
Frequency range
From 15 Hz to 400Hz
Protection
Over load
700V(between... |
Phase Sequence Indicators (Contact Type)
|
|
|
|
|
|
|
Sew 888 PMR
|
|
FEATURES
● Indicates phase rotation. ● Indicates phase presence.● Indicates motor rotation/wiring.● Indicates battery status.● Phase rotation and motor rotation indication works from as low as 1Vac.● Small, rugged enclosure.● Color coded test leads.● Phase presence indication from as low as 100 Vac. ● Very low consumption.● Fused. ● Lightweight, robust and compact.● Works from 2 Hz to 400 Hz Sine.
SPECIFICATIONS
Phase Presence Nominal Voltage for Phase Presence Indication (The voltage required for the neon Lamps L1, L2, L3 to light up).
From To Freq
100Vac 500Vac 10-400Hz
Determination of Phase Rotation Field Direction
From To Freq
1Vac 500Vac 2-400Hz
Determination of Motor Connections (requires > 1/2 turn of the shaft)
From To Freq
1Vac 500Vac 2-400Hz
Maximum Current Consumption
18mA
Over Voltage CLASS III
500V
Over Load between all terminals
500V
Battery OK goes off when battery voltage
< 6.5 Vdc
Dimensions
... |
Phase Sequence Indicators (Contact Type)
|
|
|
|
|
|
|
Sew 4156 PR
|
|
FEATURES
● The 4156 PR is used to identify the leads of a diconnected motor so that when the motor is in true phase sequence, it will run in the desired direction.
SPECIFICATIONS
Measuring ranges
0~200kΩ
Test leads
AL-34 length : 50cm
Dimensions
250(L) × 190(W) × 110(D)mm
Weight (battery included)
Approx. 1280g
Power source
1.5V (AA) × 2
Safety standard
EN 61010-1 EN 61326-1
|
Phase Sequence Indicators (Contact Type)
|
|
|
|
|