Sew 6221 EL
|
|
FEATURES
● Microprocessor-controlled.● Indicates phase rotation.● Indicates phase presence.● Tests for disconnection sensitivity.● Indicates battery status.● Tests for disconnection time.● Measures voltage phase to earth.● Select one of 3 Phase to test ELCB.● Color-coded test leads.● Phase presence indication from as low as 100Vac.● Very low consumption.● Fused earth leakage tester.● ELCB works 50Vac to 330Vac 50Hz / 60Hz.● Led indication of Voltage on ELCB.● Phase rotation and presence does not require battery to indicate.● EN 61010-1 CAT III 550V. EN 61326-1
SPECIFICATIONS
Determination of the Phase Presence
Nominal Voltage for Phase Presence Indication (the voltage required for the neon lamps L1, L2, L3 to lit up)
From 100Vac to 450Vac.
Frequency Range
From 10Hz to 400Hz.
Determination of the Phases Rotary Field Direction
Direction (the voltage required to have the direction LEDs L1-L2-L3 or L2-L1-L3 to indicates)
From 100 to 450Vac.
Frequency Range
From 2Hz to... |
Digital ELCB Testers
|
|
|
|
|
|
|
Sew DEL-101
|
|
FEATURES
● Mains wiring polarity check.● ELCB/RCD testing.● Measuring ear for line current.● Measuring ear for leakage current.● Helps calculate insulation resistance.● Helps calculate power consumption.● Helps fault finding of standing earth fault.● Fused main adapter.● Appliance testing (with the aid of a clamp meter).● Fused appliance socket.● No batteries required.● HRC fuse inside.● Fused, color-coded universal test sockets.● Universal mains IEC Lead.
SPECIFICATIONS
Voltage / power input
Universal IEC LEAD
240V/10A
Wiring polarity check
Nominal Voltage
240Vac
Frequency
50/60Hz
Mains Voltage Tolerance
±10%
Elcb / rcd tester
Nominal Voltage
240Vac
Frequency
50/60Hz
Current Tolerance (current proportional to Line to Earth Voltage)
±10%
Universal test sockets
Nominal Voltage
240Vac
Frequency
50/60Hz
Mains Voltage Tolerance
±10%
Fuse
10A
Appliance tester
Nominal... |
Multi-purpose (OLED Display)
|
|
|
|
|
|
|
Sew 6221 EL-M
|
|
FEATURES
● High contrast OLED display.● Designed for viewing in the dark, for mining industry.● Microprocessor-controlled.● Indicates phase rotation● Indicates phase presence● TEST for disconnection sensitivity● Battery status indicator● Measures Voltage Phase to Earth● Select one of 3 Phase to test ELCB.● Color-coded test leads.● Phase presence indication from as low as 100Vac.● Fused earth leakage tester.● ELCB works 50Vac to 330Vac 50Hz / 60Hz.● Phase rotation and presence does not require battery to indicate.
SPECIFICATIONS
Nominal voltage for phase presence frequency range
100Vac to 450Vac 10Hz to 400Hz
Rotary field direction phases frequency range
100 to 450Vac 2Hz to 400Hz
Overload protection
550V (between all terminal)
Over voltage protection
Class III - 450V towards ground
Current settings
999mAac /50Hz-60Hz
Phase start selection
0º and 180º
Phase polarity trip Indicator
ˇ
Operating voltage (L-E) referenced to earth
220Vac to 317Vac
Timer resolution
1ms (Max.... |
ELCB Tester (OLED Display)
|
|
|
|
|
|
|
Sew 1824 LP
|
|
FEATURES
● Microprocessor-controlled.● Measures Earth Resistance without the need for poles in the ground or external measuring wires.● Earth measurement uses the real earth current path and the current generated by the electric network, without the need for any disconnection.● The Earth Resistance displayed is exactly the earth resistance that the earth current will need to go through if an earth fault occurs. (you do not need to add all the bonding points and connection paths)● Displays voltage supply at the transformer(Line to Neutral), without loading the transformer.● Single one smart push button operation; ON, Scroll through results and menus.● Checks wiring integrity (LEDs).● Auto-off / Auto-ranging (software range).● Color-coded test leads.● Combined prospective short circuit current, loop, and earth tester.● Loop test for L-E and PSC between L-N.● Voltage test L-N.● Display can be customized for large orders.
... |
Loop Testers
|
|
|
|
|
|
|
Sew 1825 LP
|
|
FEATURES
● Microprocessor-controlled.● Measures the voltage drop as if 16A was flowing between Line and Neutral.● Displays voltage without current (V at 0A).● Display voltage as if 16A flowing between Line and Neutral (V at 16A).● Loop test for L-E● PSC between L-N.● Single one smart push button operation; ON, Scroll through results and menus.● Checks wiring integrity (LEDs).● Auto off/auto ranging (software range).● Combined prospective short circuit current, loop and load tester.● Display can be customized for large orders.
SPECIFICATIONS
Loop impedance range L-E
0.03-2000Ω (software ctrl)
Test currents in each loop
11.76A at 230V / 50Hz
Voltage measurement L-N
50 to 280V AC (Sine)
Load current for volt drop (L-N)
16A (Calculation)
Neutral wire resistance
(Not available, see 1826 NA)
Line wire resistance & transformer windings
(Not available, see 1826 NA)
PSC current (L-N) max
6kA at 230Vac supply
PSC current (L-E) max
(Not available, see 1826... |
Loop Testers
|
|
|
|
|
|
|
Sew 2811 LP
|
|
FEATURES
● Microprocessor-controlled.● Displays and sound warning if external voltage present.● Displays mains voltage, scroll trough menus.● Checks wiring integrity (LEDs and display).● Single button operation.● Auto-off/auto-ranging.● Combined prospective short circuit current, PSC and LOOP tester.● Built-in carry case, test leads in separate pouch.● Loop test for L-E and L-N and PSC.● Voltage test L-N and L-E.● Enables analysis of constituent components in L-E and L-N loops giving resistance of earth, neutral wire, live wire and transformer winding.● Display can be customized for special orders. ● 60Hz available on request.
SPECIFICATIONS
Loop impedance range L-E, L-N
20/200/2000Ω (auto-range)
Loop impedance test current
12A at 230V / 50Hz
Voltage measurement L-N, L-E
80 to 250V AC/50Hz
Earth wire/path return resistance
20/200/2000Ω (auto-range)
Neutral wire return resistance
20/200/2000Ω (auto-range)
Line wire return resistance & transformer... |
Loop Testers
|
|
|
|
|
|
|
Sew 1826 NA
|
|
FEATURES
● Microprocessor-controlled.● Measures Earth Resistance without the need for poles in the ground or external measuring wires.● Earth measurement uses the real earth current path and the current generated by the electric network, without the need for any disconnection.● The Earth Resistance displayed is exactly the earth resistance that the earth current will need to go through if an earth fault occurs. No need to add all the bonding points and connection paths resistances.● Displays voltage supply at the transformer (Line to Neutral), without loading the transformer. Displays voltage between Line (Phase) and Earth (Ground), without drawing any current.● Measures the impedance of the line itself so you can analyze and differentiate between the multiples paths of the wiring.● Measures the Neutral Impedance. Single one smart push button operation; ON,... |
Electrical Network Analyzers
|
|
|
|
|
|
|
Sew 2126 NA
|
|
FEATURES
● Microprocessor-controlled.● Built-in earth tester.● Built-in loop/psc tester. 0.03-2000Ω (software ctrl).● Built-in voltmeter.● Built-in wiring checker.● One push button smart control.● Display L-N and L-E voltages. 50 to 280Vac (sine).● Display line path impedance. 0.01-2000Ω (software ctrl).● Display earth path impedance. 0.01-2000Ω (software ctrl).● Display neutral path impedance. 0.01-2000Ω (software ctrl).● Display psc line to neutral. 6kA@230Vac> supply.● Display psc line to earth. 6kA@230Vac> supply.● Re-scroll through previous results.● Bat. ok/low battery indicator.● Auto off function.● Color-coded test leads.● Rugged case.● Ultra low power consumption.
SPECIFICATIONS
Loop / Earth / Wires
0.03-2000Ω (auto-ranging)
Prospective short circuit
0~6kA at 230Vac
Operating voltage
50V~275Vac (50Hz)
Best performance at rated voltage
230Vac ± 20V Max.10A
Accuracy of voltage
±1%(210~250V) ±3% otherwise
Accuracy of loops / earth
±2% (0.05~50Ω)
... |