Kyoritsu 6010A

Continuity and Insulation Testing

Live circuit warning LED:
Immediate illumination of a warning lamp if the circuit under test is live
Auto Discharge:
Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
Integral overload protection on internal continuity and insulation test circuitry
Autoranging
500V DC test voltage for insulation tests
200mA short circuit current on continuity ranges
Loop and RCD Testing
Wiring connection check LED’s:
Immediate indication if wiring of circuit under test is correct
Overheat Protection:
Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
Supply Voltage Indication:
Can display supply voltage value in loop impedance mode
Low Current Loop Impedance Test:
Short duration low test current will prevent tripping of many passive RCDs
Auto Data Hold:
Retains displayed reading for set period following test
Phase Angle Selection:
Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs
 
Continuity Testing
Measuring Ranges 0~19.99 and 10.0~199.9Ω (2 auto ranges)
Open Circuit Voltage > 4V (as per IEC 364)
Short Circuit Current > 200mA DC (as per IEC 364)
Accuracy |±(3% + 3dgt)
Loop Impedance Testing
Rated Voltage 230V AC +10%-15% (50Hz)
Voltage Measuring Range 100-250V AC (50Hz)
Impedance Range
Nominal Test Current
20/2000Ω
25A (20Ω range) 15mA (2000Ω range)
Test Period 1/2 cycle (10ms)
Accuracy 20Ω range : ±(3% + 8dgt)   2000Ω range : ±(3% + 8dgt)
Insulation Testing
Measuring Ranges 0~19.99 and 10.0~199.9MΩ (2 auto ranges)
Test Voltage 500V DC
Output Voltage on
Open Circuit
570V DC±6%
Rated Current > 1mA (as per IEC 364)
Accuracy |± (3% + 3dgt)
RCD Testing
Rated Voltage 230V AC +10%-15% (50Hz)
Trip Current Settings RCD × 1/2: 5, 15, 50, 150, 250mA
RCD × 1: 10, 30, 100, 300, 500mA
Trip Current Duration RCD × 1/2 × 1: 2000ms
Fast Trip 150mA
Accuracy Trip current ±3% of test current at 230V.
Trip time ±(3% + 3dgt)
General
Safety Standard IEC 61010-1 CAT.III 300V Pollution Degree 2
IEC 61010-2-031
IEC 61557
Withstand Voltage 4000V AC for 1 minute
Power Source R6P (AA) (1.5V) × 8
Dimensions 175(L) × 115(W) × 86(D)mm
Weight 780g approx.
Accessories 7122B (Test leads)
KAMP10
* (Test Lead with IEC Connector)
Pouch for Test leads
Shoulder Strap
Shoulder Pad
R6P (AA) × 8
Instruction Manual
Optional 7133B (Distribution board test leads)
* KAMP10(EU): European SHUKO plug
KAMP10(UK): British plug(13A)
KAMP10(AU): Australian plug
KAMP10(SA): South African plug